Compact unit with verifiable dispenser type FAS-120

Compact unit with verifiable dispenser type FAS-120 with counter, complete with an above-ground LPG storage tank and fittings listed below mounted on a galvanized base frame, wired, piped, primed and painted.

Execution consisting of:

  • LPG storage tanks including complete fittings
  • Submersible pump type RX33 for propane / butane, power: approx. 50 l / min at differential pressure 7.0 bar, max. Power approx. 80 l / min, max. Differential pressure 8.6 bar, three-phase motor in Ex
  • Version, power 2.2 kW, 400 V / 50 Hz, with pressure line connection system and Ex connection box
  • Overflow valve type RV18-NRV (Non-Return-Valve) and check valve
  • Ball valve DN 25
  • Solenoid valve, Ex-protected, DN 25, 230 V / 50 Hz
  • Degassing valve, pressure gauge and differential pressure switch as dry-running protection including isolating switching amplifier
  • Safety valve 25 bar
  • Ball valve as connection for differential pressure switch / dispenser
    electric dispenser type FAS-120 with special piston meter type MK-III-S, flow rate 5-50 l / min, one display, dispenser / protocol according to customer specification, power supply 230 V AC / 24 V DC, safety switch (push button), manometer, built in Stainless steel housing with protection class IP 54, high-pressure hose LPG 16, length 4.5 m, with tear-off coupling, filling gun according to customer specifications, pipe break valve in front of the hose
  • Galvanized fire protection plate and weather protection roof for submersible pump with fittings

Additional equipment / Variants:

  • available with container sizes 2.700l, 4.850l and 6.400l
  • available with external feed pump or submersible motor pump - different versions on request
  • Breakaway couplings in the dispenser base frame
  • Versions with Coriolis counter (sealless) on request
  • Electrical control cabinet for compact system control integrated for installation in the building or in the dispenser head
  • Setting up the dispenser to the container, standard = front side
  • Stairs for better accessibility of the tank fittings
  • Weather protection roof for the dispenser operator

Documentation: EU Declaration of Conformity